Range Hood Vent Code (2021 Requirements)

Probably the most important code requirement for range hoods is that they should vent outdoors.

Another important code is on the duct length and diameter of kitchen hoods.

In this code guide, I will go over…

  • Minimum duct length & diameter
  • Minimum CFM or fan speed
  • How range hoods vent to the outside
  • Makeup air systems for high powered vent hoods
range-hood-vent-code-requirements

Introduction

As a home inspector, I have inspected many range hoods over the years, and clients frequently ask me about building codes. Even though inspectors aren’t code inspectors, we do like to familiarize with building codes and best practices. In this article, I review the code requirements laid out in the IRC or the International Residential Code for range hoods.

The IRC is a ‘model code’ that many U.S. states and counties base their code on. For the final say on any code matter, you will need to consult your local state or city building codes or even a quick call to your local building department.

Even though I summarize the code requirements (I just looked at some of the most important issues), this isn’t exhaustive of every single code and exception. As a side note, older houses are almost usually ‘grandfathered in’ and not required to adhere to newer code requirements except for new installations.

Read Also: What Are The Best Cosmo Range Hoods?

What Are The Code Requirements of Range Hoods?

Exhaust Discharge 1503.3

Range hoods always need to vent to the exterior. They can’t exhaust into an attic, a crawlspace, or inside a ceiling cavity.

The main code exception is for ductless or recirculating range hoods as long as they are listed and designed for that type of installation. Recirculating range hoods always require the addition of a carbon filter which helps catch smoke and smells.

Here are a few other code requirements on how range hoods exhaust…

  • Interior of the duct should be smooth (no ridges)
  • Range hood duct needs to be air tight
  • Hood needs to have a backdraft damper (a damper or ‘flap’ closes the vent when the hood is not in use)
  • Exhaust duct needs to be independent and not connected to any other exhaust system such as a bathroom fan

Read Also: How To Install Island Range Hoods?

What Is The Required Duct Material Of Range Hoods?

Duct Material 1503.4

Range hood ducts always need to be either galvanized steel, stainless steel, or copper.

The one big exception to this code is if the range hood is a downdraft type (it sucks in air downwards and the vent goes into the floor). With a downdraft hood, it is permissible to use PVC plastic piping instead of metal under certain conditions.

What Is The Code Requirement For Makeup Air?

Makeup Air 1503.6

If you have a range hood that is rated at 400-cfm or greater, you may be required to have a makeup air system installed. Makeup air systems are automated devices with dampers that brings in fresh outdoor or to replace the air exhausted by the range hood.

This code requirement only applies to gas or propane ranges and if it isn’t already direct vented.

The makeup air unit also needs to have a damper which closes when not in use so outdoor air doesn’t leak into the home.

There are universal makeup air systems on the market such as the Nutone Universal Air 8″ Damper that uses a sensor to open the damper if it detects the range hood turned on. It only needs low voltage wiring and works well with new construction or existing kitchen hoods.

Carbon Monoxide Hazard

The main reason for the makeup air code requirement is to prevent a carbon monoxide hazard.

If you have a very strong range hood, it will create a large air pressure imbalance in the home (negative air pressure) which can possibly create a backdrafting scenario. Backdrafting is when negative air pressure actually reverses the flow of the exhaust gases into the home. If exhaust gases are going into the home rather than to the exterior, carbon monoxide poisoning can occur.

Makeup Air Should Go Into Kitchen

If you need a makeup air system by code, the ‘makeup’ or fresh air needs to be sent into the kitchen or room where the range hood is located.

The exception to this rule is that it can go into a different room as long as they are connected by a permanent opening.

The type of damper for the makeup air system should work either by gravity (opens and closed based on air flow) or it can be electronically operated. The electric dampers open automatically when the range hood is turned on.

Read Also: How To Install An Under Cabinet Ductless Range Hood?

range hood vent code requirements

What Is The Code For Duct Length?

Duct Length 1504.2

The code requirements for the duct length of range hoods is based on the duct diameter, whether it is smooth walled, and it’s CFM rating.

For example, if your range hood is rated at 200-cfm, and the flex duct has a 6-inch diameter, then the maximum duct length is 18-feet. And a 5-inch diameter sized duct or below isn’t even permitted with a 200-cfm hood and 6-inch flex duct.

The exception to this section is if the range hood satisfies the requirements of the manufacturer or if you independently test the air flow of the hood with some type of measuring device.

The X marks in the table provided below means that under these conditions a duct is not allowed because of the high pressure drop.

Read Also: What Are The Best Stainless Steel Range Hoods?

IRC Duct Length

Where Range Hood Vents Should Terminate?

Exhaust Openings 1504.3

Range hood vents should always be located on the outside and they need to terminate at least 3-feet away from windows, doors, and other vents such as bathroom fans.

If you have a powered air intake such as from a high efficiency furnace, then the range hood vent needs to be at least 10-feet away. The exception to the 10-foot rule is if the range hood vent is at least 3-feet above the intake vent.

What Is The Minimum Exhaust Rate (CFM)?

The absolute minimum CFM for a kitchen range hood is 100-cfm.

CFM stands for cubic feet per minute and it is a range hood rating for how much air the hood can exhaust every 60-seconds. Most range hoods are in the 150-350 cfm range.

What Are The Electrical Requirements of Range Hoods?

Flexible Cords 4101.3

Range hoods need to be supplied by an individual branch circuit.

For higher powered range hoods, a dedicated circuit will be needed.

The minimum cord length will be 18-inches and the maximum cord length is 48-inches.

Read Also: How To Install A Wall Mount Range Hood?

Final Thoughts

The biggest takeaway for range hood code requirements is that they need to vent to the outside. They can’t vent into a crawlspace or an attic.

Also, there are duct requirements for safety such as the length and the type of material used. If you use too small diameter of a duct, it can cause a pressure drop, and create a hazardous situation.

Another important code requirement is for makeup air.

If your range hood is 400-cfm or greater, you may need to install a makeup air system to prevent a dangerous backdrafting situation with carbon monoxide poisoning if you have fuel-burning appliances.

Other Home Guides

Looking to learn more about home maintenance? Check out our other informative home product reviews and guides!

Leave a Comment

Arie Van Tuijl

Arie Van Tuijl

I am a licensed home inspector in two U.S. states and the founder of Home Inspector Secrets. After performing hundreds of inspections, and seeing thousands of house defects, I realized people would love to have an online resource dedicated to home maintenance. I write detailed home guides and product reviews sprinkled with inspection tips. You can read my bio here.

About Home Inspector Secrets

Home Inspector Secrets is an online resource for owners, buyers, and sellers to understand all aspects of home maintenance. We have detailed home guides, product reviews, inspection advice, and much more.

Other Home Guides

Looking to learn more about home maintenance? Check out our other informative home product reviews and guides!